A1100
The A1100 is an electronic polyphase meter for domestic, commercial and light industrial direct connected or CT connected applications.
Two main versions of the A1100 meter are available. The liquid crystal display version of the meter has a choice of display formats and can be supplied with one or two rates. The meter is available as import only or import and export. The display has a customer defined display sequence that can include security information. Chevrons and legends on the nameplate identify the data being displayed.
The mechanical register version of the meter is available for kWh import one rate applications only. Five LED's are used to identify the status of the meter/system.
The A1100 offers high security with many useful security features. These include phase failure monitoring (A, B and C), reverse run (count, energy reading and alarm), power fail, phase fail and elapsed hours (rate 1, rate 2 and cumulative). These are stored as security data and can be included as part of the display sequence and read via the IrDA or serial data port.
Communication is provided via the IrDA (Infrared Data Association) port allowing the meter registers and security data to be read electronically using a hand-held device. This greatly reduces the possibility of manual meter reading errors. The meter can be configured at manufacture to provide the same absolute serial data as the IrDA port via the meter auxiliary terminals or RJ11 socket.
As an alternative to the serial data the meter can be provided with a pulse output via the auxiliary terminals. The pulse output is in accordance with SO standard (IEC 62053-31).
Automatic Meter Reading (AMR) is facilitated by either the IrDA port, serial data output or the pulsed output.
Meters can be supplied to meet accuracy EN 61036 Class 1 or Class 2 requirements or EC Directive 2004/22/EC (MID) - kWh Class A or Class B.
| Specifications | Security | Standards / Approvals | Download | ||
Features
- Accuracy - Class 1 or Class 2. MID - kWh Class A or Class B
- kWh import or kWh import/export
- Direct or CT connected
- 3 phase, 4 wire or 3 phase, 3 wire
- 16 year product life
- Large figure display (9.8mm)
- Extensive security data
- IrDA (Infrared Data Association) output for transmitting billing, security and status data
- 12 kV isolation
- Compact design
- Double insulated, glass filled polycarbonate case to DIN 43857 part 2 and part 4 (except for top fixing centres)
- IP53 in accordance with EN 60529 : 1991
Options
- Liquid Crystal Display or mechanical register
- One or two rates controlled by an external device
- CT or Direct Connected
- Auxiliary terminals configured for:
- Rate selection (two rate meters)
- Pulsing output
- Serial data output
- Terminal cover with or without cut-out
| LCD Meter | Mechanical Meter | |||
| Event | LCD | IrDA / Serial | LED | IrDA / Serial |
| Phase A Present | + | + | ||
| Phase B Present | + | + | ||
| Phase C Present | + | + | ||
| Reverse Event Count | + | + | + | |
| Reverse Run Energy Reading | + | + | + | |
| Reverse Alarm | + | + | ||
| Power Fail Count | + | + | + | |
| Phase Fail Count | + | + | + | |
| Elapsed Hours Rate 1 | + | + | + | |
| Elapsed Hours Rate 2 | + | + | + | |
| Elapsed Hours Cumulative Display | + | |||
| Meter Error | + | + | + | + |
The A1100 conforms to:
- The essential requirements of the directive 2004-22/EC on Measuring Instruments (MID)
- The general requirements and particular requirements of EN 50470 Parts 1 & 3, and complies with Class M2 Mechanical environment and Class E2 Electromagnetic Environment.
- IEC 62053 - 21 kWh, Class 1 & Class 2 Static
- EN 50470 1-3 kWh Class A or B
- EC Directive 2004/22/EC (MID) Class A and B
- DIN 43857 Parts 2 and 4 Dimensional Requirements (except for top fixing centre)
- The degree of ingress protection is to IP53, IEC 60529:1989
- Meters are marked with the European CE mark, in accordance with the Marking Directive 93/68/EEC, to indicate compliance with the requirements of the EMC Directive 89/336/EEC.
- The A1100 meter measures active energy, according to the requirements of EN 61036 1996 (plus amendment 1:2000) for indoor kWh meters of protective Class II and accuracy Class 1 or Class 2
- Brochure Download (pdf) 549 KB